CyberPower RT33030KE Rack Tower 30kVA/24kW UPS (MIC)

฿214,210.00 (รวมภาษี)
฿200,196.26 (ไม่รวมภาษี)

รหัสสินค้า: RT33030KE

มีสินค้าอยู่ 100

CyberPower RT33030KE

 

CyberPower RT33030KE guarantees power backup protection for IT equipment such as FTTx devices, networking devices and NAS/storage devices. The product adopts double conversion online topology, and it is typically integrated in the back office, server room, and data center environment.

With integrated IGBT technology and intelligent DSP-based control, the RT33 UPS produces less input total harmonic distortion (THDi), achieving higher power efficiency. The system also intelligently controls the whole process of the charging and discharging, effectively improving the life time of the battery. The system can be configured to 3-in/3-out or 3-in/1-out according to the users’ needs. The product is of rack modular design, compatible with 19” standard rack cabinet. Its 5.5” touchscreen color LCD with graphic display provides more information and is easier for customer to operate. The LCD display can also be configured to vertical or horizontal display through LCD setting.

 

Features :

  • Three-phase Design

  • ECO Mode

  • Flexible System Configuration

  • Rack Modular Design

  • Color LCD Panel

  • Dual Inputs

  • Generator Compatible

  • Battery Cold Start

  • SNMP/HTTP Remote Management Capability (Optional)

  • Extended Battery Module (EBM) 

  • Online (Double Conversion) UPS Topology

  • High Density Design

  • High Output Power Factor

  • Rack/Tower Convertible Configurations

  • LCD Touch Panel

  • UPS Parallel Expansion

  • Pure Sine Wave Output

  • Smart Battery Management (SBM)

  • PowerPanel Management Software

 

Specifications :

General
Phase Three Phase
Form Factor Rackmount, Tower
UPS Topology Online Double Conversion
Energy Saving Technology ECO Mode Efficiency > 98%
Normal Mode Efficiency (%) 95.5%
Battery Mode Efficiency (%) 95.5%
Active PFC Compatibility Yes
Parallel Expansion (Max. Units) 4
Input
Dual Power Inputs Yes
Generator Compatibility Yes
Nominal Input Voltage (Vac) Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Input Voltage Range (Vac) Line to Neutral (L-N): 132 ~ 276 Vac, Line to Line (L-L): 228 ~ 478 Vac
Configurable Voltage Range (Vac) Line to Neutral (L-N): 220 ~ 250 Vac, Line to Line (L-L): 380 ~ 435 Vac
Input Frequency (Hz)

50 ± 3

60 ± 3

Input Frequency Range (Hz) 40 ~ 70
Rated Input Current (A) 37
Input Power Factor 0.99
Input Connector Type Hardwire Terminal Block
Output
Capacity (VA) 30000
Capacity (Watts) 24000
On Battery Waveform Pure Sine Wave
Output Voltage Setting Configurable
Output Frequency Setting Configurable
Rated Output Voltage (Vac) Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Output Voltage Tolerance (%) 1.5%
Output Frequency (Hz ± %)

50 ± 0.1

60 ± 0.1

Power Factor 0.8
ECO Mode Voltage Tolerance ±10%
Overload Protection Internal Current Limiting, Circuit Breaker, Fuse
Overload Protection (Line Mode) 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Battery Mode) 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Bypass Mode) 125~130% Load for 10 min, 130~150% Load for 1 min, 150~400% Load for 1 sec, >400% Load Immediately
Crest Factor 3:1
Harmonic Distortion (Linear Load) THD<1%
Harmonic Distortion (Non-linear Load) THD<6%
Internal Bypass Automatic Bypass, Manual Bypass
Outlet Type Hardwire Terminal Block x 1
Typical Transfer Time (ms) 0
Battery
Compatible Battery Types VRLA, AGM, Gel, Wet
Recharge Power (%) Default 10% (Selectable from 1~20% x UPS Capacity)
Recharge Power Setting Configurable
Charger Voltage Tolerance (%) ≤1%
Start On Battery Yes
Smart Battery Management (SBM) Yes
User-replaceable No
Battery Solution Extended Battery
Battery Voltage (V) ±240 (480)
Compatible Extended Battery Module (EBM) BM240V63ART3U
Compatible Extended Battery Cabinet (EBC) SMBF17, SMBF20, SMBF26, SMBF40, SMBF65, BCA100N125, BCA12N63, BCA20N125, BCA40N125
External Battery Quantity 12V x 40pcs
Surge Protection & Filtering
EMI/RFI Filtration Yes
Management & Communications
LCD Panel Yes
LCD Types Color LCD, LCD Touch Panel
LCD Orientation Rotatable LCD – Manual
LCD Information Display Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log
LCD Setting & Control Mode Setting, Input & Output, Battery Setting, Communication, Event & Log, Security Setting, Language
LED Indicators Yes
Serial Port RS232 x 1 + RS485 x 1 + Dry Contact x 1
Dry Contact (with Relay) Yes
Audible Alarms Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery
Management Cable (pcs) Power Cord x1
Power Management Software PowerPanel Business (Recommended)
SNMP/HTTP Remote Monitoring Yes – with optional RMCARD205
Physical
Compatible with Racks (3 Phase) Yes
Enclosure Construction Metal
Color Black
Ingress Protection IP20
Rackmount Rail Yes
Rackmount Ears Yes
High Density Design Yes
Physical Size – UPS Module
Dimensions (WxHxD) (mm.) 438 x 130 x 750
Weight (kg.) 27
Installed Rack Height (U) 3
Shipping Dimensions
Dimensions (WxHxD) (mm.) 575 x 270 x 950
Weight (kg.) 34
Environmental
Operating Temperature (°C) 0 ~ 40
Operating Relative Humidity (Non-condensing) (%) 0 ~ 95
Operating Elevation (feet/meters) ≤1000, Load Derated 1% per 100m from 1000m and 2000m
Storage Temperature (°C) -40 ~ 70
Storage Relative Humidity (Non-condensing) (%) 0 ~ 95
Audible Noise at 1.0M from Surface of Unit (dBA) 58
Certifications
Certifications CE, BSMI, IEC62040-1, IEC62040-2