CyberPower HSTP3T200KE 200KVA/180KW 400/230VAC 3PHASE w/o BAT
รหัสสินค้า: HSTP3T200KE
มีสินค้าอยู่ 100
Product successfully added to the Quote List
CyberPower HSTP3T200KE
CyberPower HSTP3T200KE 3-Phase online UPS provides long-lasting power backup for data closets, transportation and infrastructure, and emergency systems. With parallel expansion capability, the HSTP3T (3-Phase) Series UPS is ideal for critical applications in server rooms, data centers, industrial factories, and power generation plants that require high capacity, high reliability, and extended runtimes.
With integrated IGBT technology and intelligent DSP-based control, the UPS produces less input total harmonic distortion (THDi) and achieves higher power efficiency up to 98% in Economy Mode, making it the most efficient UPS in the industry. Higher operating efficiency equates to lowered BTU heat dissipation and lowered idle power consumption, resulting in an operating expense reduction and a lower carbon footprint.
To improve operating efficiency, the UPS system works in bypass mode under normal conditions, during which the inverter is kept on standby. During power failures, the UPS switches to battery mode and supplies backup power to the connected critical load.
Features :
-
Three-phase Design
-
Hot-swappable Power Modules
-
LCD Touch Panel
-
UPS Parallel Expansion
-
Generator Compatible
-
Overload Protection
-
LCD Status Display
-
SNMP/HTTP Remote Management Capability (Optional)
-
Online (Double Conversion) UPS Topology
-
ECO Mode
-
Color LCD Panel
-
Dual Inputs
-
Pure Sine Wave Output
-
Maintenance Bypass Switch
-
Emergency Power Off (EPO) Port
-
PowerPanel Management Software
Specifications :
| General | |
| Phase | Three Phase |
| Form Factor | Tower |
| UPS Topology | Online Double Conversion |
| Energy Saving Technology | ECO Mode Efficiency > 98% |
| Normal Mode Efficiency (%) | 96% |
| Battery Mode Efficiency (%) | 96% |
| Active PFC Compatibility | Yes |
| Parallel Expansion (Max. Units) | 4 |
| Input | |
| Dual Power Inputs | Yes |
| Generator Compatibility | Yes |
| Nominal Input Voltage (Vac) | Line to Neutral (L-N): 220, 230, 240 Vac Line to Line (L-L): 380, 400, 415 Vac |
| Input Voltage Range (Vac) | Line to Neutral (L-N): 132 ~ 276 Vac Line to Line (L-L): 228 ~ 478 Vac |
| Configurable Voltage Range (Vac) | 220 ~ 250 Vac Line to Line (L-L): 380 ~ 435 Vac |
| Input Frequency (Hz) | 50 ± 3 60 ± 3 |
| Input Frequency Range (Hz) | 40 ~ 70 |
| Rated Input Current (A) | 275 |
| THDI (%) | <3% (Linear Load) |
| Input Power Factor | 0.99 |
| Input Connector Type | Hardwire Terminal Block |
| Output | |
| Capacity (VA) | 200000 |
| Capacity (Watts) | 180000 |
| On Battery Waveform | Pure Sine Wave |
| Output Voltage Setting | Configurable |
| Output Frequency Setting | Configurable |
| Rated Output Voltage (Vac) | Line to Neutral (L-N): 220, 230, 240 Vac Line to Line (L-L): 380, 400, 415 Vac |
| Output Voltage Tolerance (%) | 1% |
| Output Frequency (Hz ± %) | 50 ± 0.1 60 ± 0.1 |
| Power Factor | 0.9 |
| ECO Mode Voltage Tolerance | ±10% |
| Overload Protection | Internal Current Limiting, Circuit Breaker, Fuse |
| Overload Protection (Line Mode) | 105~110% Load for 60 min 110~125% Load for 10 min 125~150% Load for 1 min >150% Load Immediately |
| Overload Protection (Battery Mode) | 105~110% Load for 60 min 110~125% Load for 10 min 125~150% Load for 1 min >150% Load Immediately |
| Overload Protection (Bypass Mode) | 125~130% Load for 10 min 130~150% Load for 1 min 150~400% Load for 1 sec >400% Load Immediately |
| Crest Factor | 3:1 |
| Harmonic Distortion (Linear Load) | THD <1% |
| Harmonic Distortion (Non-linear Load) | THD <5% |
| Internal Bypass | Automatic Bypass, Manual Bypass |
| Maintenance Bypass | Yes |
| Outlet Type | Hardwire Terminal Block x 1 |
| Typical Transfer Time (ms) | 0 |
| Battery | |
| Compatible Battery Types | VRLA, AGM, Gel, Wet |
| Recharge Power (%) | Default 10% (Selectable from 1~20% x UPS Capacity) |
| Recharge Power Setting | Configurable |
| Charger Voltage Tolerance ( % ) | ≤ 1 % |
| Smart Battery Management (SBM) | Yes |
| User-replaceable | No |
| Battery Solution | Extended Battery |
| Battery Voltage (V) | ±240 (480) |
| Compatible Extended Battery Cabinet (EBC) | SMBF17, SMBF20, SMBF26, SMBF33, SMBF40, SMBF65, BCA100N125, BCA12N63, BCA20N125, BCA40N125 |
| External Battery Quantity | 12V x 40pcs |
| Surge Protection & Filtering | |
| EMI/RFI Filtration | Yes |
| Management & Communications | |
| LCD Panel | Yes |
| LCD Types | Color LCD, LCD Touch Panel |
| LCD Information Display | Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log |
| LCD Setting & Control | Mode Setting, Input & Output, Battery Setting, Communication, Event & Log, Security Setting, Language |
| LED Indicators | Yes |
| Serial Port | RS232 x 1 + RS485 x 1 + Dry Contact x 1 |
| Dry Contact (with Relay) | Yes |
| Emergency Power Off (EPO) Port | Yes |
| Audible Alarms | Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery |
| Power Management Software | PowerPanel Business (Recommended) |
| SNMP/HTTP Remote Monitoring | Yes – with optional RMCARD205 |
| Physical | |
| Enclosure Construction | Metal |
| Color | Black |
| Ingress Protection | IP20 |
| Physical Size – UPS Module | |
| Dimensions (WxHxD) (mm.) | 650 x 1600 x 960 |
| Weight (kg.) | 350 |
| Shipping Dimensions | |
| Dimensions (WxHxD) (mm.) | 800 x 1810 x 1110 |
| Weight (kg.) | 383 |
| Environmental | |
| Operating Temperature (°C) | 0 ~ 40 |
| Operating Relative Humidity (Non-condensing) (%) | 0 ~ 95 |
| Operating Elevation (feet/meters) | ≤1000, Load Derated 1% per 100m from 1000m and 2000m |
| Storage Temperature (°C) | -40 ~ 70 |
| Storage Relative Humidity (Non-condensing) (%) | 0 ~ 95 |
| Certifications | |
| Certifications | CE, IEC62040-1, IEC62040-2 |